EcoCatcher Project
Independent Project · Building Physics & Sustainable Design

EcoCatcher: a low-cost, zero-grid windcatcher for a warming world

Rebuilding the Persian bâdgir and Gulf barjeel with recycled, solar-powered parts — and testing, city by city, where it can replace air-conditioning.

Maksud Yusuf & Jamal Naghizade Baku, Azerbaijan Version 2.0 · October 2026 Independent project
Project summary

Space cooling is among the fastest-growing sources of electricity demand on Earth, and the growth is concentrated in hot countries whose grids still burn fossil fuels. This project revisits the windcatcher, a passive-cooling tower used across Iran, the Arabian Gulf, Egypt and Pakistan for centuries, and asks whether six inexpensive upgrades — an evaporative pad fed by greywater, a solar chimney, solar-powered fans, sensor-driven louvers, dust mesh and a thermal-mass lining — can make it a credible substitute for air-conditioning in a single room. A transparent physics model combining wind-pressure and stack-driven ventilation, evaporative cooling, a room heat balance and first-order thermal mass is run hour by hour against the ASHRAE 55 adaptive comfort criterion. For a simulated Riyadh summer day (peak –), the full design holds the room's peak at –, stays inside the comfort band for – of 24 hours, and avoids roughly – of CO₂ a year for a build cost of –. Screening 24 hot-climate cities shows that the design works well in hot-dry regions, needs hybrid operation in moderately humid ones, and should not be relied on in humid tropical climates.

Keywords: passive cooling · windcatcher · evaporative cooling · natural ventilation · thermal comfort · low-cost housing · climate adaptation

Key figures · Riyadh, full design
Peak outdoor
–
Peak indoor
–
Comfort hours
–
Grid electricity
0 kWh
Build cost
–
CO₂ avoided / yr
–
Payback
–
Pad water / day
–
Computed live by the model in §2. Change units or currency at the top of the page.
§ 1

Introduction

Cooling is the fastest-growing use of energy in buildings. The International Energy Agency estimates that air-conditioners and electric fans already account for roughly a tenth of all electricity consumed worldwide, and that the global stock of air-conditioners could roughly triple by 2050 [1]. Most of that growth will happen in hot countries where grids still run largely on fossil fuels and where many households can afford neither the units nor the bills. Rising heat makes the problem self-reinforcing: every new air-conditioner exhausts heat into the street and carbon into the atmosphere.

Long before electricity, builders across the Middle East and South Asia solved the same problem with architecture. The windcatcher — bâdgir in Persian, barjeel in Gulf Arabic, malqaf in Egypt — is a tower that rises above the roof to catch the prevailing breeze, where wind is stronger and air is cleaner, and funnels it down into the rooms below, while openings on the leeward side pull stale air out [5, 6]. The historic city of Yazd in central Iran, inscribed on the UNESCO World Heritage List in 2017, is still crowned by hundreds of them [11].

Traditional towers have three well-known weaknesses. They do little when the air is still; they let in dust, insects and birds; and in very hot weather they move hot air rather than cool air unless water is added. Modern engineering literature has proposed fixes — evaporative columns, solar chimneys, mechanical assistance [7, 12] — but most are designed for commercial buildings and priced accordingly. EcoCatcher asks whether the same ideas can be delivered at the scale and budget of a single family room.

Design challengeCan a traditional windcatcher, upgraded only with low-cost, recycled and solar-powered parts, keep a typical 20 m² room within the adaptive comfort band through a hot-climate summer day — without drawing any electricity from the grid?

What this project delivers

  1. A modular design of six upgrades, each under US$45 and buildable with hand tools from salvaged or locally available materials (§6).
  2. An open, transparent physics model combining wind pressure, stack effect, evaporative cooling and thermal mass, running hour by hour in any browser, offline, in seven languages (§2–3).
  3. A global screening of 24 hot-climate cities that identifies where the design works on its own, where it needs hybrid operation, and where it should not be used (§4–5).
  4. A validation plan with instruments, metrics and pass criteria so the model can be tested against a physical prototype (§7).
§ 2

Interactive model

Choose a city or set your own climate, switch upgrades on and off, and move through the day. Every number on this page — including the abstract — is recomputed by the same model.

Interactive model available in 7 languages; the report text is in English.

Live cross-section

coolwarmhot
Time of day 15:00

Results at selected hour

Outside
–
Indoor (est.)
–
Airflow
–
Supply air
–
Comfortable hours
–
Pad water use
–
Indoor humidity
–
Feels like
–
–
Annual economics
Build cost
–
Payback
–
AC energy saved / yr
–
Money saved / yr
–
CO₂ avoided / yr
–
Grid electricity used
0 kWh

Mixed-mode assumption. Simplified teaching model.

Climate & context

Peak outdoor temperature
Humidity at peak
Wind speed
Day–night swing
Room floor area
Cooling season
Electricity price
Grid carbon intensity

Modern upgrades — select to toggle

§ 3

Method

The model is deliberately simple: every equation is printed here, every constant is listed in Table 1, and the complete source code is in this page. It is intended for comparing design options and climates, not for certifying a building. The day is simulated in 15-minute steps over four consecutive identical days so that the thermal-mass response settles; the fourth day is reported.

3.1 Diurnal climate

Outdoor temperature follows a cosine between the daily minimum and the peak at 15:00. Absolute humidity is held constant through the day, so relative humidity rises at night as the air cools — the physically consistent behaviour of a dry desert night. The dew point is found with the Magnus approximation [8], and wind is taken as 25 % weaker at night than in the afternoon.

T(h) = Tmax − ΔTday/2 · [1 − cos(2π(h − 15)/24)](1)

3.2 Airflow

Wind-driven flow through the tower is proportional to wind speed and the square root of the pressure-coefficient difference between windward and leeward openings; stack-driven flow is proportional to the square root of the temperature rise in the exhaust shaft, which the solar chimney increases in sunlight [9, 12]. The two combine in quadrature, and the solar fans add a fixed flow in daylight.

Qw = Cd A v √ΔCp,   Qs = Cd A √(2gHΔTs / T),   Q = √(Qw² + Qs²) + Qfan(2)

3.3 Evaporative cooling

Air passing the wet pad approaches its wet-bulb temperature, computed with Stull's empirical formula [2], with a pad effectiveness ε. Without a pad, contact with the cool tower walls gives a small effect (ε = 0.10). The water evaporated is the sensible heat removed divided by the latent heat of vaporisation.

Tsup = T − ε (T − Twb),   ṁwater = ρ cp Q (T − Tsup) / hfg(3)

3.4 Room heat balance and thermal mass

Internal and solar gains G (people, devices and sun through the envelope) warm the supply air on its way through the room, giving a steady-state room temperature. The real room lags behind that target with a time constant τ that is short for a lightweight room and long for a clay or rammed-earth lining, which is how thermal mass carries night-time coolness into the afternoon.

Tss = Tsup + G / (ρ cp Q),   dTin/dt = (Tss − Tin) / τ(4)

3.5 Comfort criterion

Naturally ventilated buildings are judged with the ASHRAE 55 adaptive model [3, 4], under which people accept warmer rooms when the outdoor climate is warmer. The neutral temperature depends on the prevailing mean outdoor temperature, and the 80 % acceptability band extends 3.5 K either side.

Tcomf = 0.31 Tout,mean + 17.8,   Tupper,80 = Tcomf + 3.5(5)

Evaporative cooling trades heat for moisture, and the adaptive model alone would rate a cool but saturated room as comfortable. The room's vapour pressure e is therefore taken from the supply air (evaporation follows a line of constant wet-bulb temperature), and comfort is judged on Steadman's still-air apparent temperature [13], which penalises humid air and rewards dry air.

e = es(Twb) − γ (Tsup − Twb),   Tfeel = Tin + 0.33 e − 4.0   (e in hPa)(5b)

Climate zones in Figure 3 and Table 2 follow the peak-hour wet-bulb temperature, the usual screening rule for direct evaporative cooling: A up to 22.5 °C, B 22.5–25.5 °C, C above 25.5 °C.

3.6 Energy, cost and carbon

The baseline is a sealed room cooled by a split air-conditioner to 25 °C. EcoCatcher is assumed to run in mixed mode: the air-conditioner switches on only in hours when the room leaves the comfort band. The fraction of cooling load avoided is scaled to a baseline annual consumption, then multiplied by the local tariff and grid carbon intensity [10].

f = 1 − ΣTin>Tupper(Tin − 25) / Σ(T − 25)+,   Esaved = f · eAC · Afloor · months(6)
Table 1Model parameters and assumptions.
SymbolMeaningValueBasis
ATower opening area (0.6 × 0.6 m)0.36 m²Design choice, single-room scale
CdDischarge coefficient0.60Typical sharp-edged opening [9]
√ΔCpRoot of pressure-coefficient difference0.55Mid-range of reported wind-tower values [6]
HStack height, room to tower outlet6 m3 m tower above a 3 m room
ΔTsExhaust temperature rise1.5 K (+9 K × sun with chimney)Solar-chimney studies [12]
QfanSolar fan flow (3 × 140 mm fans)0.12 m³/s, daylight onlyFree-air rating; no battery
εPad effectiveness / wall effect0.70 / 0.10Low-cost fibre pads, conservative
—Pad, mesh, louver flow factors×0.85, ×0.92, ×1.20 (×1.45 night)Assumed resistance / control gain
GInternal + solar gains25 + 30 × sun W/m²Two occupants, devices, sun on envelope
τRoom time constant (light / heavy)2.5 h / 10 hOrder-of-magnitude for earth walls
γPsychrometer constant (sea level)0.667 hPa/KStandard psychrometry
eACBaseline AC energy12.5 kWh/m² per month≈ 1 500 kWh/yr for 20 m², 6 months
§ 4

Results

The three figures below update with the scenario selected in §2. They show what happens over a full day, which upgrades actually earn their cost, and where in the world the physics allows the design to work.

Figure 124-hour profile — The indoor curve lags and flattens the outdoor curve; the shaded band is the range of temperatures that 80 % of occupants find acceptable.
Figure 2Ablation. . Effects interact, so they do not add up exactly.
Figure 3Climate suitability map. Zone boundaries are lines of constant wet-bulb temperature (22.5 °C and 25.5 °C).

Key findings

  1. Humidity, not heat, decides feasibility. A 46 °C afternoon in Kuwait is easier to cool than a 33 °C afternoon in Mumbai: the dry air has a far larger wet-bulb depression to exploit, and the extra moisture stays tolerable (Figure 3). In Dubai, Karachi, Mumbai and Singapore the room still feels too hot, so the design should not be used there without dehumidification.
  2. The evaporative pad and the thermal-mass lining do most of the work in hot-dry climates (Figure 2). Together they cost about US$65, roughly a quarter of the full design.
  3. The solar chimney and fans matter most on calm days. With wind below about 1 m/s they supply most of the airflow, which is why they are kept despite small effects in windy cities such as Baku.
  4. Payback depends more on tariffs than on climate. Heavily subsidised electricity in parts of the Gulf and Iran stretches payback past a decade even where the cooling is excellent; the carbon and grid-peak benefits remain.
  5. Water is the hidden cost. In a Riyadh summer the pad evaporates about – a day — similar to a household's entire greywater output. The design therefore specifies greywater or air-conditioner condensate rather than drinking water, and the controller should stop wetting the pad whenever the room is already comfortable.
§ 5

Global atlas

Full EcoCatcher design, 20 m² room.

Table 2Screening of 24 hot-climate locations under the full design. Select a column heading to sort.

Climate inputs are indicative design-day values for the hottest month (peak temperature, afternoon humidity, typical wind), and tariffs and grid intensities are rounded national or regional figures. They are suitable for screening, not design. For a real site, replace them with an EPW weather file and the local tariff.

§ 6

Materials & cost

Table 3Bill of materials for the configuration selected in §2.
ComponentMaterial choiceCost
Total
Table 4Regional material substitutions — designing for local supply chains.
ComponentGulf & Middle EastSouth AsiaSub-Saharan AfricaLatin AmericaMediterranean · Australia · US Southwest
Tower bodyCompressed earth blocks, gypsum plasterReclaimed fired brick, lime plasterStabilised earth or laterite blocksAdobe, bahareque (wattle and daub)Rammed earth, reclaimed brick
Evaporative padDate-palm fibreJute, or vetiver (khus) matsCoconut coir, sisalAgave or sisal fibre, coirAspen wood-wool cooler pads
Frame & slatsReclaimed timber, palm-rib (jareed)BambooBamboo, eucalyptus polesGuadua bambooReclaimed timber
Chimney absorberReused aluminium or tin sheetFlattened oil tinsCorrugated roofing offcutsGalvanised sheet offcutsReused steel roofing
Pad waterAir-conditioner condensate, ablution greywaterBath and kitchen greywater, rainwaterHarvested rainwaterGreywater, rainwaterRainwater, greywater
§ 7

Limitations & validation plan

An honest model states where it may be wrong. The most important limitations, roughly in order of how much they could change the conclusions:

  1. Uncalibrated parameters. Discharge coefficient, pressure coefficients and pad effectiveness are taken from the literature, not measured on this tower. Real towers vary widely with geometry and wind direction [6, 7].
  2. Steady, one-dimensional airflow. The model ignores gusts, changes in wind direction, and short-circuiting, where incoming air leaves through the leeward opening without reaching the room. Computational fluid dynamics (CFD) or wind-tunnel tests are needed to quantify it.
  3. Indoor humidity is approximated. The room takes the supply air's vapour pressure; moisture from occupants, cooking and plants is ignored. The humidity penalty uses Steadman's apparent temperature, which is not part of ASHRAE 55, so humid-climate comfort results remain uncertain.
  4. Adaptive comfort outside its range. ASHRAE 55 defines the adaptive model only for prevailing mean outdoor temperatures up to 33.5 °C; hotter cases are clamped to that limit [3].
  5. Idealised climate. One design day per city stands in for a whole season. Heatwaves, dust storms and humid spells are not represented.
  6. Water quality and hygiene. Greywater on a pad needs filtering and regular drying cycles to prevent odour and microbial growth. The design avoids aerosol sprays, but the risk is not zero.
  7. Embodied carbon and cost. Prices are indicative, and the carbon in the materials themselves is not yet counted.
Table 5Validation plan.
StageSet-upInstrumentsMetricPass criterion
1 · Pad bench testPad in a duct with a box fan; dry and wet runsTwo SHT31 temperature–humidity sensors (±0.2 °C)Measured effectiveness εWithin ±0.10 of model
2 · Scale airflow1:5 tower on a plywood room, fan as wind, incense smoke for visualisationVane or hot-wire anemometerQ vs. v slope, i.e. Cd√ΔCpModel error < 25 %
3 · Full-scale pilotOne roof room, 2–4 summer weeks, tower vs. identical control roomESP32 logger, 4 sensors, water meter, local weather stationHourly indoor RMSE; litres per dayRMSE < 1.5 °C
4 · Occupant comfortShort survey of consenting occupantsASHRAE 7-point thermal-sensation scale + loggerVotes between −1 and +1≥ 80 % of votes
§ 8

Roadmap & future work

  1. Phase I · Prototype

    Build and instrument a 1:5 model

    Plywood room, earth-plaster lining, removable pad. Log temperature, humidity and airflow every minute with an ESP32.

  2. Phase II · Calibrate

    Fit the model to measurements

    Estimate ε and Cd√ΔCp from data, report the error before and after calibration, and publish the dataset openly with a DOI.

  3. Phase III · Higher fidelity

    CFD and full-year simulation

    Model the tower in OpenFOAM or SimScale to quantify short-circuiting. Run a full year with real EPW weather files in EnergyPlus or Ladybug Tools.

  4. Phase IV · Pilot

    One real room, one real summer

    Install on a school or community building on the Absheron peninsula and compare it with an identical control room.

  5. Phase V · Share

    Open-source kit and publication

    A multilingual build guide, a peer-reviewed student paper, and science-fair entries. Partner with NGOs working on heat resilience in informal housing.

§ 9

References

  1. International Energy Agency (2018). The Future of Cooling: Opportunities for energy-efficient air conditioning. Paris: IEA.
  2. Stull, R. (2011). Wet-bulb temperature from relative humidity and air temperature. Journal of Applied Meteorology and Climatology, 50(11), 2267–2269.
  3. ASHRAE (2020). ANSI/ASHRAE Standard 55-2020: Thermal Environmental Conditions for Human Occupancy. Atlanta: ASHRAE.
  4. de Dear, R. J., & Brager, G. S. (1998). Developing an adaptive model of thermal comfort and preference. ASHRAE Transactions, 104(1), 145–167.
  5. Bahadori, M. N. (1985). An improved design of wind towers for natural ventilation and passive cooling. Solar Energy, 35(2), 119–129.
  6. Hughes, B. R., Calautit, J. K., & Ghani, S. A. (2012). The development of commercial wind towers for natural ventilation: A review. Applied Energy, 92, 606–627.
  7. Montazeri, H., & Azizian, R. (2008). Experimental study on natural ventilation performance of one-sided wind catcher. Building and Environment, 43(12), 2193–2202.
  8. Alduchov, O. A., & Eskridge, R. E. (1996). Improved Magnus form approximation of saturation vapor pressure. Journal of Applied Meteorology, 35(4), 601–609.
  9. CIBSE (2005). AM10: Natural Ventilation in Non-Domestic Buildings. London: Chartered Institution of Building Services Engineers.
  10. Ember (2024). Global Electricity Review 2024 and yearly electricity data. London: Ember.
  11. UNESCO World Heritage Centre (2017). Historic City of Yazd (inscription 1544).
  12. Bansal, N. K., Mathur, R., & Bhandari, M. S. (1994). A study of solar chimney assisted wind tower system for natural ventilation in buildings. Building and Environment, 29(4), 495–500.
  13. Steadman, R. G. (1994). Norms of apparent temperature in Australia. Australian Meteorological Magazine, 43, 1–16.

Cite this project

@misc{yusuf2026ecocatcher,
  author       = {Yusuf, Maksud and Naghizade, Jamal},
  title        = {EcoCatcher: A Low-Cost, Zero-Grid Windcatcher for a Warming World},
  year         = {2026},
  month        = oct,
  note         = {Interactive project edition, version 2.0},
  howpublished = {Online}
}